BEST LEDR-1

BEST LEDR-1 LED Emergency Light User Manual

Model: LEDR-1

1. Pendahuluan

This manual provides essential instructions for the safe installation, operation, and maintenance of your BEST LEDR-1 LED Emergency Light. Please read this manual thoroughly before installation and retain it for future reference. The LEDR-1 is designed to provide reliable emergency illumination during power outages, ensuring safety in commercial and residential environments.

2. Petunjuk Keselamatan Penting

WARNING: Risk of electric shock. Disconnect power before installation or servicing.

  • Semua servis harus dilakukan hanya oleh personel yang berkualifikasi.
  • Jangan memasang di dekat pemanas gas atau listrik.
  • Ensure the electrical wiring is properly grounded.
  • Do not use outdoors. This unit is designed for indoor use only.
  • Jangan biarkan kabel catu daya menyentuh permukaan yang panas.
  • Mount the unit in locations and at heights where it will not be subjected to tampoleh personel yang tidak berwenang.
  • Penggunaan peralatan aksesori yang tidak direkomendasikan oleh produsen dapat menyebabkan kondisi yang tidak aman.
  • Jangan menggunakan peralatan ini untuk tujuan lain selain yang dimaksudkan.
  • Allow battery to charge for a minimum of 24 hours after installation before testing.

3. Isi Paket

Verifikasi bahwa semua komponen ada dan tidak rusak saat membuka kemasan:

  • BEST LEDR-1 LED Emergency Light Fixture (1 unit)
  • Perangkat Keras Pemasangan (sekrup, jangkar)
  • Kacang Kawat
  • User Manual (dokumen ini)
  • AA NiCAD Battery (pre-installed or included separately)

4. Produk Lebihview

The BEST LEDR-1 is a compact and efficient LED emergency light designed for wall-mount applications. It features a durable white thermoplastic housing and two adjustable LED lamp heads, providing 98 lumens of bright, white light (5000 Kelvin) during emergency situations. The unit operates on 120 Volts AC and includes a rechargeable NiCAD battery for backup power.

BEST LEDR-1 Emergency Light, front view

Gambar 1: Depan view of the BEST LEDR-1 Emergency Light. This image shows the compact white thermoplastic housing with two adjustable LED lamp kepala.

Fitur Utama:

  • Perumahan: White Thermoplastic
  • Sumber Cahaya: 2 LED heads
  • Jil.tage: 120 Volts AC
  • Baterai: NiCAD, 90 minutes average life
  • Keluaran Cahaya: 98 lumen cahaya
  • Ukuran: Ukuran kurang lebih 14.75" P x 3.75" L x 3.75" T

5. Instalasi

The LEDR-1 is designed for flush wall mounting. Follow these steps for proper installation:

  1. Pemutusan Daya: Before beginning any installation, ensure that the main power supply to the circuit where the emergency light will be installed is turned OFF at the circuit breaker or fuse box.
  2. Lokasi Pemasangan: Select a suitable wall location for mounting. The unit should be mounted at a height and in a position that allows for optimal light distribution during an emergency. Ensure the mounting surface is solid and can support the fixture's weight.
  3. Siapkan Permukaan Pemasangan: Use the provided mounting hardware (screws and anchors) to secure the mounting plate or backplate of the emergency light to the wall. If the unit has a separate mounting plate, attach it first.
  4. Koneksi Kabel:
    • Hubungkan kabel hitam from the emergency light to the hot (live) wire from the building's electrical supply.
    • Hubungkan kabel putih from the emergency light to the kabel netral from the building's electrical supply.
    • Hubungkan kabel hijau from the emergency light to the kabel tanah from the building's electrical supply.
    • Use the provided wire nuts to secure all connections. Ensure all connections are tight and properly insulated.
  5. Koneksi Baterai: If the battery is not pre-connected, connect the battery pack to the circuit board. Ensure correct polarity.
  6. Perlengkapan Aman: Carefully tuck all wires into the junction box or fixture housing. Secure the emergency light fixture to the mounting plate or wall according to the specific design of the unit.
  7. Pulihkan Daya: Once the installation is complete and all connections are secure, restore power to the circuit. The CHARGE INDICATOR light on the unit should illuminate, indicating that the battery is charging.
  8. Tagihan Awal: Allow the battery to charge for a minimum of 24 hours before performing the first test.

6. Operasi

The BEST LEDR-1 Emergency Light operates automatically:

  • Daya AC Hidup: When AC power is supplied to the unit, the charge indicator light will be ON, and the battery will be charging. The LED lamp heads will remain OFF.
  • Power Otage: In the event of an AC power failure, the emergency light will automatically switch to battery backup mode, and the LED lamp heads will illuminate. The unit will provide emergency lighting for approximately 90 minutes.
  • AC Power Restored: When AC power is restored, the LED lamp heads will turn OFF, and the unit will revert to charging the battery.
  • Tombol Uji: A test button is located on the unit. Pressing this button simulates an AC power failure, allowing you to verify that the emergency lights function correctly. Release the button to return to normal operation.
  • L yang dapat disesuaikanamp Kepala: The two LED lamp heads can be manually adjusted to direct light to desired areas.

7. Pemeliharaan

Regular maintenance ensures the longevity and reliability of your emergency light.

Pengujian Baterai:

Perform the following tests according to local codes and regulations (typically monthly and annually):

  • Tes Bulanan: Press and hold the test button for at least 30 seconds. The LED lamp heads should illuminate. Release the button; the lights should turn off, and the charge indicator should be ON.
  • Tes Tahunan: Disconnect AC power to the unit for a full 90 minutes. The LED lamp heads should remain illuminated for the entire duration. Reconnect AC power; the lights should turn off, and the charge indicator should be ON. If the unit fails to operate for the full 90 minutes, the battery may need replacement.

Pembersihan:

Clean the exterior of the unit and lamp heads periodically with a soft, damp kain. Jangan gunakan pembersih atau pelarut yang bersifat abrasif.

Penggantian Baterai:

The NiCAD battery has a limited lifespan. If the unit fails the annual 90-minute test, the battery likely needs replacement. Contact a qualified electrician or the manufacturer for battery replacement instructions and compatible battery types.

8. Penyelesaian masalah

MasalahKemungkinan PenyebabLarutan
Emergency lights do not turn ON during power outage or when test button is pressed.
  • No AC power to the unit.
  • Battery not connected or faulty.
  • Baterai tidak terisi penuh.
  • Faulty LED lamp kepala.
  • Periksa pemutus sirkuit dan sambungan kabel.
  • Ensure battery is properly connected. Allow 24 hours for initial charge.
  • Perform a 90-minute discharge test after 24-hour charge. Replace battery if necessary.
  • Hubungi personel servis yang berkualifikasi.
Charge indicator light is OFF when AC power is present.
  • No AC power to the unit.
  • Faulty charge indicator LED.
  • Kesalahan sirkuit internal.
  • Periksa pemutus sirkuit dan sambungan kabel.
  • Hubungi personel servis yang berkualifikasi.
Emergency lights do not stay ON for 90 minutes during annual test.
  • Baterai telah mencapai akhir masa pakainya.
  • Baterai tidak terisi penuh.
  • Ganti baterainya.
  • Ensure unit has been connected to AC power for at least 24 hours prior to test.

9. Spesifikasi

FiturDetil
Nomor ModelLEDR-1
MerekTERBAIK
Bahan PerumahanWhite Thermoplastic
Jenis Sumber CahayaLED (2 heads)
Jil.tage120 Volts AC
Apatage2 watt
Kecerahan98 lumen cahaya
Efisiensi49 lumen/watt
Suhu Warna5000 Kelvin
Jenis BateraiNiCAD (1 AA battery required, included)
Average Battery Life (Emergency Mode)90 menit
Jenis InstalasiSiram Pemasangan Dinding
Penggunaan Dalam/Luar RuanganHanya di dalam ruangan
Dimensi Produk (P x L x T)14.75" x 3.75" x 3.75"
Berat Barang0.01 Ons
Metode KontrolRemote (Test Button)

10. Garansi dan Dukungan

The BEST LEDR-1 LED Emergency Light comes with a full manufacturer warranty. For specific warranty details, claims, or technical support, please refer to the warranty card included with your product or contact Best Lighting Products directly. Keep your purchase receipt as proof of purchase.

For assistance, please contact Best Lighting Products customer service.

Ask a question about this manual