AKO CAMRegis Basic

Peringatan
- Unit harus dipasang di tempat yang terlindung dari getaran, air, dan gas korosif, di mana suhu sekitar tidak melebihi nilai yang ditunjukkan dalam data teknis.
- For the unit to operate correctly, use only the probes supplied by AKO. For the reading to be correct, the probe should be used in a place without heat influences apart from the temperature you want to me-asure or control.
- Probe dan kabelnya TIDAK PERNAH dipasang di saluran bersama dengan kabel daya, kontrol, atau pengumpan.
- In the event of lengthening the NTC probe, always used shield cable and earth the mesh. In these cases, the maximum deviation will be 0.25 ºC from -40 ºC to +20 ºC (Maximum 1000 m with a minimum section of 0.5 mm2 ).
- We recommend using AKO-15586 cable. Always disconnect the power supply to do the wiring.
- The power circuit should be equipped with a switch marked as dis-connecting device of the equipment of at least 2 A, 230 V, situated near the appliance.
- The power supply cable should be H05VV-F or H05V-K type. The gauge will depend on local regulations, but should in no case be less than 1 mm2 . The electrical installation should be carried out under pipe. Using the logger not observing the manufacturer’s instructions may alter the appliance safety requirements. Only probes supplied by AKO should be used for the appliance to operate correctly.
Instalasi

DIMENSI

Spesifikasi teknis
- Power supply……………………………………………… 90-240 V~ 50/60Hz
- Alarm relay…………………………………………………………… 8 A cos j=1
- NTC range (AKO-14931)…………………………………. -50 ºC to 99.9 ºC
- Range 4-20 mA…………. Configurable from -100 to 900 (1000 levels)
- Resolution ………………………………………………………………………..0,1
- Accuracy class (-40 ºC to 40 ºC):………………….. ±1 ºC acc/ EN 12830
- Response time:……………………………………………………. < 20 seconds
- Maximum relative time error:…………………………………………< 0.1 %
- Marked according to UNE-EN 12830……………..S,A,1,-40 ºC + 40 ºC
- ………………………………………………………… Cocok untuk digunakan dalam penyimpanan (S)
- …………………………………………………………..Tipe lingkungan iklim (A)
- ………………………………………………………………………….. Kelas akurasi (1)
- Maximum input power……………………………………………………8.5 VA
- Working ambient temperature…………………………………0 ºC to 40 ºC
- Storage ambient temperature……………………………… -20 ºC to 60 ºC
- Degree of protection…………………………………………………………IP40
- Insulasi ganda antara catu daya, sirkuit sekunder, dan keluaran relai.
- Installation category……………………………………… II acc/ EN 61010-1
- Pollution degree…………………………………………… II acc/ EN 61010-1
- Maintenance of date and time without power supply……Up to 2 days
- Internal buzzer………………………………………………….. 70dB at 30 cm
- SD cards accepted……………………………………SD/SDHC (FAT / FAT32)
Pengkabelan

Operasi
Fungsi utama
key: A short press displays the maximum value reached in the last 24h, and the time when all the active inputs were reached. In the programming menu it allows scrolling around the different levels, or during the setting of a parameter, changing its value.
key: A short press displays the minimum value reached in the last 24h, and the time when all the active inputs were reached. In the programming menu it allows scrolling around the different levels, or during the setting of a parameter, changing its value.
key: A short press downloads the data of the ongoing log onto the SD card (if it has been inserted)
key: A short press downloads ALL the logged data onto the SD card (if it has been inserted). The save without changes, return to previous level or exit programming parameter appears on the programming menu.- SET key: A short press downloads the data of the last log onto the SD card (if it has been inserted).
- Membungkam alarm akustik (menurut parameter P50).
- Dalam pemrograman, konfirmasikan pilihan dan simpan nilai yang dimasukkan.
keys : Pressing for over 10 seconds accesses the data log display menu.- Tekan
untuk memilih blok log dan tekan SET untuk mengaksesnya. - Tekan
untuk memilih log yang akan ditampilkan, setelah 1 detik nilai dari setiap masukan akan ditampilkan, menunjukkan tanggal dan waktu log. - N + O keys : Pressing for over 10 seconds accesses the alarms log display menu.
Press N / Q to select the input to be displayed and press SET.
Press N / Q to select the event to be displayed (no. 1 is the most recent event), after 1 second the value of each input will be displayed, indicating the date and time of the event.
keys: Pressing them for over 10 seconds accesses the programming menu.


Struktur data yang dicatat
- Data yang dicatat disimpan dalam memori internal logger yang diatur dalam blok log. Periode waktu yang disimpan di setiap blok, dan kapasitas maksimum memori internal, bergantung pada interval log (parameter L1), seperti yang ditunjukkan pada tabel.
- Logger memiliki slot untuk kartu SD, yang memungkinkan mentransfer data yang disimpan untuk ditampilkan di komputer atau untuk disimpan sebagai cadangan. Data ini disimpan dalam format spreadsheet (.csv), diatur dengan cara berikut:
PENTING: Do not remove the SD card until the indicator turns off. The download may take several minutes depending on the data saved.


- Downloads ALL the logged data (P key)
Dua files dihasilkan yang namanya tahun, bulan dan hari pengunduhan, dalam dua folder berbeda SEMUA dan ALARM. Yang pertama berisi file dengan semua data yang dicatat oleh perangkat hingga saat itu dan yang kedua berisi file dengan acara yang disimpan hingga saat itu (lihat bagian 5.2): - Log alarm
This function saves an event whenever an alarm is activated or deactivated. To download the events log data, press the P key, all the data logged up to date are downloaded onto the SD card, including the events log, contained in the “ALARMS” folder. - Memulai awal
Tanggal dan waktu akan diminta selama start-up pertama.

Menu pemrograman (parameter)
To access the parameter programming menu, press the N + Q keys at the same time. Refer to the list of available parameters in section 5 of this manual. After 20 seconds without touching any key, the unit returns to the previous level. If it is in level 3 the changes will not be saved.

Tabel parameter dan pesan
Def. kolom menunjukkan parameter default pabrik. Kecuali dinyatakan lain, nilai suhu dinyatakan dalam ºC (suhu setara dalam ºF).
| Level 1 Menu dan deskripsi | |||||
| In P | Konfigurasi masukan tingkat 2 | ||||
| Deskripsi Tingkat 3 | menit | Def. | Maksimum | ||
| i1 | Jenis input 1: 0: Dinonaktifkan 1: NTC 2: 4-20 mA 3: Input digital (NO) 4: Input digital (NC) | 0 | 1 | 4 | |
| i2 | Nilai 4 mA masukan 1 | -100 | 0 | i3 | |
| i3 | Nilai 20 mA masukan 1 | i2 | 100 | 900 | |
| i4 | Masukan kalibrasi 1 | -20 | 0 | 20 | |
| Bahasa Indonesia: i11 | Jenis input 2: 0: Dinonaktifkan 1: NTC 2: 4-20 mA 3: Input digital (NO) 4: Input digital (NC) | 0 | 0 | 4 | |
| Bahasa Indonesia: i12 | Nilai 4 mA masukan 2 | -100 | 0 | Bahasa Indonesia: i13 | |
| Bahasa Indonesia: i13 | Nilai 20 mA masukan 2 | Bahasa Indonesia: i12 | 100 | 900 | |
| Bahasa Indonesia: i14 | Masukan kalibrasi 2 | -20 | 0 | 20 | |
| EP | Keluar ke Tingkat 1 | ||||
| AL | Konfigurasi Alarm Tingkat 2 | ||||
| Deskripsi Tingkat 3 | menit | Def. | Maksimum | ||
| A0 | Masukan alarm 1: 0: Dinonaktifkan; 1: Diaktifkan | 0 | 0 | 1 | |
| A1 | Input nilai alarm MAX 1 | A2 | 99.9 | 999* | |
| A2 | Masukan nilai alarm MIN 1 | -999* | -50 | A1 | |
| A3 | Input alarm tunda 1 | 0 | 0 | 120 | |
| A4 | Input output alarm 1: 0: Tidak ada output 1: Hanya akustik 2: Hanya relai 3: Akustik + relai | 0 | 0 | 3 | |
| Nomor telepon A10 | Masukan alarm 2: 0: Dinonaktifkan; 1: Diaktifkan | 0 | 0 | 1 | |
| Nomor telepon A11 | Input nilai alarm MAX 2 | Nomor telepon A12 | 0 | 999* | |
| Nomor telepon A12 | Masukan nilai alarm MIN 2 | -999* | 0 | Nomor telepon A11 | |
| Nomor telepon A13 | Input alarm tunda 2 | 0 | 0 | 120 | |
| Nomor telepon A14 | Input output alarm 1: 0: Tidak ada output 1: Hanya akustik 2: Hanya relai 3: Akustik + relai | 0 | 0 | 3 | |
| EP | Keluar ke Tingkat 1 | ||||
| Cn F | Level 2 Konfigurasi umum | ||||
| Deskripsi Tingkat 3 | menit | Def. | Maksimum | ||
| P2 | Fungsi kode akses: 0: Tidak aktif; 1: Blok akses parameter | 0 | 0 | 1 | |
| P3 | Parameter default: 0:Tidak; 1: Ya | 0 | 0 | 1 | |
| P5 | Alamat MODBUS untuk unit dengan komunikasi | 1 | 1 | 255 | |
| P7 | Temperature display mode: 0: Integers in ºC 1: One decimal point in ºC2: Integers in ºF 3: One decimal point in ºF | 0 | 1 | 3 | |
| P8 | Input yang akan ditampilkan: 0: Carrusel Input 1 – Input 2; 1: Masukan 1; 2: Masukan 2 | 0 | 1 | 2 | |
| Bagian 50 | Matikan alarm dengan tombol SET: 0: Dinonaktifkan 1: Hanya suara 2: Hanya relai 3: Suara dan relai | 0 | 1 | 3 | |
| EP | Keluar ke Tingkat 1 | ||||
| d LG | Konfigurasi Logger Level 2 | ||||
| Deskripsi Tingkat 3 | menit | Def. | Maksimum | ||
| L1 | Log interval: 0: 1 minute 1: 5 minutes 2: 15 minutes3: 30 minutes 4: 60 minutes | 0 | 2 | 4 | |
| L2 | Hapus catatan dan log peristiwa: 0:Tidak; 1: Ya | 0 | 0 | 1 | |
| L3 | Day of the start of the log: 0: Monday 1: Tuesday 2: Wednesday 3: Thursday4: Friday 5: Saturday 6: Sunday | 0 | 0 | 6 | |
| L4 | Pemisah desimal dalam .csv files: 0: , 1: . | 0 | 0 | 1 | |
| EP | Keluar ke Tingkat 1 | ||||
| r tC | Tingkat 2 Tanggal dan waktu | ||||
| Deskripsi Tingkat 3 | menit | Def. | Maksimum | ||
| r1 | Jam | 0 | 0 | 23 | |
| r2 | Menit | 0 | 0 | 59 | |
| r3 | Hari | 1 | 1 | 31 | |
| r4 | Bulan | 1 | 1 | 12 | |
| r5 | Tahun | 12 | 12 | 99 | |
| r6 | Perubahan jam otomatis: 0: Tidak; 1: Ya | 0 | 1 | 1 | |
| EP | Keluar ke Tingkat 1 | ||||
| waktu | Level 2 Kontrol akses dan Informasi | ||||
| Deskripsi Tingkat 3 | menit | Def. | Maksimum | ||
| L5 | Kata sandi | 0 | – | 99 | |
| PU | Versi program | – | – | – | |
| Pr | Revisi program | – | – | – | |
| EP | Keluar ke Tingkat 1 | ||||