Perkenalan
The AEMC Model 3711 is a portable clamp-on ground resistance tester designed for measuring electrical ground rod and grid resistance in multi-grounded systems. This instrument offers a non-intrusive method for testing without the need for auxiliary rods or disconnecting the ground system. It also measures leakage, neutral, and phase currents, providing a comprehensive solution for electrical system analysis.
Informasi Keselamatan
PERINGATAN: Always read and understand all safety instructions before operating this instrument. Failure to do so may result in serious injury or death.
- This instrument is rated CAT III, indicating its suitability for measurements in building installations.
- Adhere to all local and national safety codes and regulations.
- Do not use the instrument if it appears damaged or is operating abnormally.
- Pastikan kompartemen baterai tertutup rapat sebelum digunakan.
- Avoid contact with live circuits during measurement.
- The instrument is double-insulated for enhanced safety.
Apa yang ada di dalam kotak
Verifikasi bahwa semua barang ada saat membongkar:
- AEMC Ground Resistance Tester Model 3711
- Calibration Check Loop, 25Ω
- Tas jinjing keras
- Baterai Alkaline 9V
- User Manual (dokumen ini)
Produk Selesaiview

Image: The AEMC Model 3711 Clamp-On Ground Resistance Tester. This image displays the device with its red clamp jaws open, a black body, and a green digital display showing "9.8 Ω". Control buttons are visible below the display.
The AEMC Model 3711 features an ergonomic design for one-handed operation. Its robust polycarbonate construction ensures durability for outdoor use. Key components include:
- Clamp Mulut: 1.25" opening to accommodate ground rods and cables up to 1000kcmil.
- Layar LCD: Digital readout for resistance and current measurements.
- Tombol Kontrol: For power, data hold, and mode selection.
- Kompartemen Baterai: Located at the rear for a 9V battery.
Pengaturan dan Pemasangan Baterai
- Open the battery compartment cover on the rear of the instrument.
- Insert the supplied 9V Alkaline battery, observing correct polarity.
- Tutup penutup ruang baterai dengan rapat.
- Press the "ON" button to power on the device. The display should illuminate.
Petunjuk Pengoperasian
Ground Resistance Measurement
- Power on the AEMC 3711.
- Buka clamp rahang dengan menekan tuas pelepas.
- Tempatkan clamp around the ground conductor or rod to be tested, ensuring the jaws are fully closed.
- The instrument will automatically measure and display the ground resistance in Ohms (Ω).
- For stable readings, allow approximately one second for the measurement to settle.
- To hold the current reading on the display, press the "HOLD" button. Press again to release.
Pengukuran Arus
- Power on the AEMC 3711.
- Buka clamp mulut.
- Tempatkan clamp around the conductor carrying the current to be measured (leakage, neutral, or phase current). Ensure the jaws are fully closed.
- The instrument will automatically measure and display the current in Amperes (A) atau miliAmpere (mA).
- The current measurement function provides direct readings for leakage current flowing to ground or circulating in ground loops (down to 1mA) and neutral/phase currents (up to 30A RMS).
Pemeliharaan dan Kalibrasi
Pembersihan
Bersihkan alat dengan lembut, damp kain. Jangan gunakan pembersih atau pelarut yang bersifat abrasif.
Penggantian Baterai
When the low battery indicator appears on the display, replace the 9V battery as described in the "Setup and Battery Installation" section.
Pemeriksaan Kalibrasi
Use the supplied 25Ω calibration check loop to verify the instrument's accuracy periodically. Clamp the tester around the loop; the reading should be approximately 25Ω. If the reading deviates significantly, contact AEMC customer support for service.
Penyimpanan
Store the instrument in its hard carrying case in a dry, cool environment when not in use. Remove the battery if storing for extended periods.
Penyelesaian Masalah
- No Display/Instrument Not Powering On: Periksa pemasangan baterai dan pastikan baterai memiliki daya yang cukup. Ganti jika perlu.
- Pembacaan Tidak Stabil: Pastikan kliamp jaws are fully closed around the conductor. Verify there is no excessive electrical noise in the environment.
- "OL" atau Indikasi Kelebihan Beban: The measured value exceeds the instrument's range. Ensure the correct measurement function is selected or the circuit parameters are within the device's limits.
- Pembacaan yang Tidak Akurat: Perform a calibration check using the 25Ω loop. If the issue persists, contact technical support.
Spesifikasi
| Parameter | Nilai |
|---|---|
| Rentang Resistansi Tanah | Autoranging 0.01 to 1200Ω |
| Rentang Pengukuran Saat Ini | Autoranging 1mA to 30.00A RMS |
| Resistance Measuring Frequency | frekuensi 2403Hz |
| Current Measuring Frequency | 47 hingga 800Hz |
| Accuracy (Resistance) | ±2% reading ±0.02Ω (up to 25% of reading for 600-1200Ω) |
| Suhu Operasional | -10 hingga 55°C (14 hingga 131°F) |
| Sumber Daya | Baterai 9V (termasuk) |
| Berat | 1kg (2.2 pon) |
| Dimensi (T x L x D) | 235 x 100 x 55mm (9.25 x 3.94 x 2.17 inci) |
| Pembukaan Rahang | 1.25 inci |
| Peringkat Keamanan | EN 61010, CAT III, UL approved, CE marked |
Garansi dan Dukungan
For warranty information, technical support, or service inquiries, please refer to the official AEMC Instruments websitus web atau hubungi layanan pelanggan mereka. Simpan struk pembelian Anda untuk klaim garansi.